Utilizing SC300 Series Signal Conditioners with AC900 Series Sensors
SC300 Series Signal Conditioners are compatible CTC's AC900 series hazardous rated sensors. Please note that SC300s are not hazardous rated. This means that they must be located outside of the hazardous environment in accordance with your hazardous-rated protocol. For Intrinsically Safe (Class 1, Division 1 / Zone 0,1) applications, cabling from the sensor must be run through a barrier. Cabling may then be run from the barrier to a Signal Conditioner Enclosure located outside of the hazardous environment. Signal Conditioners and barriers may be located in the same enclosure, as long as it is outside of the hazardous area. For Non-Arcing applications, (Class 1, Division 2/Zone2) approved cabling may be run directly to the Signal Conditioner Enclosure so long as the enclosure is located outside of the hazardous environment.